Installation
Guidelines for Slim Line Series Air Handlers
When choosing the proper model Slim Line Air Handler(SLM),
primary consideration should be given to calculated
BTU loads and available power supply.
Slim Line Series air handlers are designed to be direct-discharge
or ductable units. Air flow can be supplied to more
than one area through the use of properly sized plenums,
transitions and ductwork. The SLM configuration allows
for installation in tight areas (shipside panels,
narrow bulkhead spaces, short overheads, etc.) in
either horizontal or vertical positons.
Securely fasten the SLM units to a solid level surface
using the sour (4) mounting holes provided in the
base. The supply air outlet must be sealed properly
either through cabinetry for direct-discharge, or
into a plenum for a ductable discharge, All ductwork
is to be routed as amooth and direct as possible.
Any flexible ducting is to be secured every 48"(minimum)
to prevent movement while the vessel is under operation.
Trim off excess ducting before making final connections.
The return air inlet(s) must be properly sized and
located to allow adequate air flow into the air handler.
The SLM series air handlers have factory installed,
removable filters to trap dust and airborne particles.
These filters must be accessible for maintenance.
Return air inlets should not be located in such a
way as to allow the supply air stream to blow directly
into its opening. This will cause "short cycling"
of the unit, resulting in poor or inadequate performace.
The supply air grille(s) must be sized and located
to allow for proper air circulation within the cabin
area(s). Grille locations close to the ceiling, or
directed upward, provide the best air circulation.
Undersized grilles and plenums, along with crushed
or kinked ductwork, will result in poor or inadequate
performace.
Both condensation drain lines must be connected to
air the handler's two(2) drain spuds using reinforced
flexible hose(5/8") and clamps. The drains may be
teed together, providing there is a minimum drop of
2" from the drain pan to the tee fitting. For installations
on sailboats that heel over 15°, position air
handlers so that the condensate pans drain port and
starboard and use drains teed together. Properly secure
the drain lines to prevent movement or lifting during
vessel operation. Check the drains upon completion
by pouring two(2) quarts of water into the drain pan.
Note: Condensation drain line may need to be insulated
when located in overhead lockers to prevent sweating
of the line, which could cause water damage.
Never install your air conditioner air handler in
bilge or engine room areas. Insure that the selected
location is sealed from direct access to bilge and/or
engine room vapors. Do not terminater condensate drain
lines within four(4) feet of any outlet of engine
or generator, nor in a bilge(vapours can travel up
the drain lines), unless the drain is connected properly
to a sealsed condensate or shower sump pump. Failure
to comply may allow bilge or engine room vapours to
mix with the air conditioners return air and contaminate
living areas.
Water connections from the circulation circuit to
the unit are to be reinforced flexible hose and double
clamped, direction of clamps should be reversed. Attach
the hose to hte hose barb fittings on the water inlet
and outlet of the unit. All hose, pipe and connections
must be insulated properly to prevent condensation.
Use approved closed cell tude insulation (1/2" minimum)
on the hose, and foam tape on fittings (5-6 wraps).
All wiring must be sized according to marine design
standards. Only stranded, tinned copper is to be used.
All electrical connections to the air handler are
to be made inside the electrical junction boxes provided
on the assembly. All units must be properly grounded.
|