|
Installation
Guidelines for 6K - 16K Condensing Units
When choosing the proper model Condensing Unit,
primary condsideration should be given to calculated
BTU loads and available power supply. Speial consideration
should be given in determining the reverse cycle heating
capacities under anticipated conditions. Reverse cycke
operation is affected by the seawater temperature.
As it decreases, the unit's heat transfer capacity
also decreases and proportionately affects the output
of warm air. It is not recommended that the unit be
operated in the heat cycle with water temperatures
below 40°F.
The location of the Condensing Unit should
be dry and accessible for service, and provide the
most direct routing of refrigerant line sets relative
to the evaporator location(s). The vibration isolated
condensing unit should be secured to a horizontal
shelf that is designed for the weight of the unit
and torsion loads from the vessel's movement.
Refrigerant-grade copper tubing should be properly
sized for the specific application. Both the suction
and liquid lines should be insulated separately with
approved closed cell foam jackets(i.e., 1/4" wall
thickness insulation). The refrigerant line ends should
remain capped until the actual connections are made
to prevent contamination. To prevent kinks in the
tubing, which will adversely affect the performace
and longevity of the system, tube benders are recommended.
When using multiple evaporators with one condensing
unit, locate all unions and tee fittings properly
in area accessible for service. Use approved flaring
techniques and refrigerant grade components for all
connections.
Insulate fittings using insulation tape (only after
system has been leak-checked). Wrap fittings sufficiently
to equal R-value of tube insulation. Reinforced marine
grade hose should be used for the seawater circuit.
All hose fittings should be double clamped. The hose
should be routed upward from the thru hullintake to
prevent air locking. The condensation drain should
be connected and routed downward to a proper sump
or overboard discharge.
All circuit breakers and wire gauge must be sized
according to marine design standards. Only stranded
tinned copper wire should be used. All equipment must
be properly grounded.
The installed line sets and evaporator(s) must be
evacuated to remove air from these components and
prevent moisture acidity formation. All connections
should be propoerly leak-checked upon releasing the
refrigerant charge from the condensing unit into the
system. If the system is to opened for any reason
at this point or for future service, the refrigerant
charge must be "pumped down" back into the condensing
unit or recovered to prevent it from escaping into
the atmosphere.
Refer to other individual components sheets for specifications
and details of evaporators, controls and related parts.
In keeping with regulations set forth by the EPA,
only certified technicians should perform service
on, or make adjustments to, the refrigerant circuit.
Never install your sir handler in bilge or engine
room areas. Insure that the selected location is sealed
from direct access to bilge and/or engine room vapors.
Do not terminate condensate drain lines within three(3)
feet of any outlet of engine or generator, nor in
a bilge(vapor can travel up the drain line), unless
the drain is connected properly to a sealed condensate
or shower sump pump. Failure to comply may allow bilge
or engine room vapors to mix with the air conditioners
return air and contaminate living areas.
|